Database last updated on Sat, 07 Feb 2026 05:10:55 +0000 by localhost

Critical warnings from b-files' comments for days between 2022061 and 2022061 (0 sec, 17 rows)

TypeCommentcountpriorityfnamelocationserialtimevalueminmax
rl:2022 061 22 27 42 Attempt to exceed max boundary293B06122.239CHURC#23906:31:531-1
rl:2022 061 22 27 42 <M,10,-1:M,10,501>473B06122.239CHURC#23906:31:551-1
rl:2022 061 22 27 42 <M,10,-1:M,10,501>295B06122.239CHURC#23906:31:551-1
rl:2022 061 22 41 49 Reset Warm -> Warm from 2022 061 22 41 45 until 2022 061 22 41 46 . Counts: 0,1213B06122.239CHURC#23906:33:581-1
rl:2022 061 22 41 50 Motor #11: appears stuck with a reference sensor activated.341B06122.239CHURC#23906:34:011-1
rl:2022 061 22 41 50 Motor #11: appears stuck with a reference sensor activated.213B06122.239CHURC#23906:34:011-1
rl:2022 061 22 43 58 MAIN.C : motor initialization timed out.125B06122.239CHURC#23906:34:031-1
rl:2022 061 22 45 06 Bad command string. Command string buffer cleared.183B06122.239CHURC#23906:34:071-1
rl:2022 061 22 45 06 Bad command string. Command string buffer cleared.183B06122.239CHURC#23906:34:071-1
rl:2022 061 00 25 35 Motor #10: appears stuck with a reference sensor activated.133B06122.239CHURC#23906:38:061-1
hp:Spectrometer alignment trouble.71B06122.239CHURC#23910:50:211-1
hg:Lamp not on... hg test terminated F1= 0 F4= 081B06122.239CHURC#23911:03:091-1
hg:Lamp not detected f1= 0 f4= 051B06122.239CHURC#23911:03:101-1
hg:No intensity detected. Check PMT.31B06122.239CHURC#23911:03:101-1
fr:11000 steps - QUIT - Micrometer #1 reference not found61B06122.239CHURC#23911:04:361-1
hg:HG failed21B06122.239CHURC#23914:03:55failed1-1
hg:Brewer failed to respond 5 times41B06122.239CHURC#23920:01:391-1

Instrument constant changes for the week before 2022061 (2 sec, 0 rows)

Hg with step corrections larger than 10 steps or multiple corrections larger than 2.5 steps (0 sec, 1 rows)

SerialYYYYJJJHG largemax correction
23920220612618.3

HP with step corrections larger than 20 steps (0 sec, 1 rows)

SerialYYYYJJJHP largemax correction
2392022061146.0

Non-critical warnings from b-files' comments for days between 2022061 and 2022061 (0 sec, 6 rows)

TypeCommentcountpriorityfnamelocationserialtimevalueminmax
ds:DS intensity too low ( 1/cy), skipping.199B06122.239CHURC#23900:04:331-1
zs:ZS intensity too low ( 1/cy), skipping.199B06122.239CHURC#23900:04:501-1
rl:Log item overwritten by later entry.13B06122.239CHURC#23906:31:511-1
rl:2022 061 22 34 42 New value set for watermark LOOP.RUN.TIME: 714.000034 millisec.13B06122.239CHURC#23906:32:191-1
rl:2022 061 22 34 42 New value set for watermark LOOP.RUN.TIME: 714.000034 millisec.13B06122.239CHURC#23906:32:191-1
menu:BACKSPACE key pressed45B06122.239CHURC#23912:41:341-1

Measurements and tests summary.


_jday_loc_serial_skcdtedhghprssluv
061CHURCHILL#239Attempting recovery FR,ecsc,HOME key pressed,menu,Must do HG now,Next schedule will be ecsc (now ecsc ZS= 93 ZS= 102.216),Next schedule will be ecsc (now ecsc ZS= 93 ZS= 93.95)222314233
(0 sec)

Number of days since last dome/window cleaning (0 sec, 3 rows)

serialdays
239more than a year
3more than a year

Missing files (0 sec, 1 rows)

Seriallast datadays ago
23920220620-1

Run/Stop results for last week. (0 sec, 1 rows)

SerialTotalFailed 0Failed darkFailed 1Failed 2Failed 3Failed 4Failed 5Failed double
239200000000

AP results for SB Brewers. (0 sec, 1 rows)

SerialJdayt1 offt1 ont2 offt2 ont3 offt3 onHV offHV on+12V off+12V on+5V off+5V on-12V off-12V on+24V off+24V on+5V sps off+5V sps onSL A offSL A onSL V offSL V onWatts
23920220615.45.45.25.1-5.5-5.51349.71349.412.012.05.05.0-12.0-12.024.724.25.05.00.01.50.010.9915.9

Suspicious HG test results (correlation<0.98 or counts<5000). (0 sec, 1 rows)

SerialJdaycountPeakmin.corr.max.corr.30-day history
#2390617875390.93590.9836